The Kruger KDD 9/9 T 550W is a double inlet, double width (DIDW) direct driven centrifugal fan with a forward curved impeller, suitable for air handling units, fan coil units and other OEM airside equipment. It is fitted with a 550 W, 4-pole, single-phase 230 V 50 Hz capacitor motor with three speeds (high / medium / low), and has a galvanised steel housing and impeller.
The motor is an open-housing type rated IP21 with Class F insulation, thermal protection and ball bearings greased for life, with the capacitor fitted on the fan housing. The impeller is statically and dynamically balanced to ISO 1940 and AMCA 204, grade G2.5. Mounting feet (allowing three inlet discharge positions) and an outlet flange are available as accessories.
Technical specifications
|
| Model | KDD 9/9T 550W 4P-1 3S P |
| Fan type | Double inlet, double width centrifugal |
| Impeller | Forward curved, galvanised steel |
| Drive arrangement | Direct drive |
| Motor output | 550 W |
| Poles | 4 |
| Supply | Single phase, 230 V, 50 Hz |
| Speeds | 3 (H / M / L) |
| Nominal speed | 1290 / 1210 / 1150 rpm (H / M / L) |
| Maximum airflow | 3,557 m³/h |
| Maximum current | 5.99 / 4.85 / 4.05 A (H / M / L) |
| Capacitor | 16/450 µF/V |
| Motor protection | IP21, Class F insulation |
| Sound pressure Lp(A) at 3 m | 63 / 63 / 61 dB(A) (H / M / L), inlet, free discharge |
| Operating temperature | −20°C to +40°C |
| Fan weight | 15.6 kg |
Specifications are taken from Kruger’s KDD-P series brochure (LEA163.E0) for the 50 Hz model.
Selection: Delivered airflow and pressure depend on the system resistance and the selected speed; the maximum airflow figure is at free delivery. Refer to the KDD-P performance curves for the duty point.